System Schematic
Before installing anything on the mains incomer it is wise to conduct a technical audit of the technology. These pages outline why powerPerfector leads the industry in savings and reliability.

Ask a VPO® Expert...

Our expert team are on hand to answer all your Voltage Power Optimisation needs, simply fill out the form below and we’ll be in touch.

Reason for enquiry
  • General
  • Technical
  • Purchasing
  • Student

Thank you for
your question.

A member of the
powerPerfector team will get in contact with you shortly, if your question is urgent please call:
0207 164 2271.
If you would like to ask another question please

Click here

System Schematic

Link for this page:
/Schematic.png?v=1

Primary Winding

This winding is in series with the site’s power supply and carries the load current on each phase. It is constructed from heavy-gauge copper sheets, with very few turns, meaning that the unit has very low impedance and very low losses. This winding acts to filter harmonics and protects the site from common transient events.


Secondary Winding

The interaction between the primary and secondary winding on each phase acts to reduce the voltage by a fixed percentage. For example, if V in is around 240V, V out will be 220.8V, assuming an 8% optimisation setting. Each powerPerfector unit has four optimisation settings and a 0% setting.

An example of a typical optimisation setting range is -5%, -6%, -7%, -8% and a 0%.

The connection between each phase has a current flowing that is in direct proportion to the difference between the three phase voltages. This connection forms an unreferenced star point on the secondary side. In this way, the powerPerfector is able to compensate for imbalanced phase voltages without recourse to active (electronic or mechanical) components.


Tertiary Winding

These are connected as a closed ‘delta’ configuration. The purpose of the closed loop is to provide a path to circulate and dissipate harmonic currents present on the incoming supply, thus attenuating and preventing them from circulating into the downstream load. This winding has the same effect on harmonic currents that are generated downstream of the powerPerfector unit, preventing harmonic currents that are generated on site from circulating into the upstream load.


*The greengauge represents the aggregate savings of powerPerfector installations in the UK, Ireland, Cyprus and Denmark. Savings correct at the time of installation using either IPMVP savings analysis or reasonable estimates, where savings analysis was not possible. Actual savings may change over time for example due to energy pricing, occupancy, equipment, rates, building re-purposing and further energy efficiency measures.

All content copyright of powerPerfector Ltd 2015. All rights reserved.